Skip to main content

Division 4 - Masonry

SECTION 042000 - UNIT MASONRY PART 1 - GENERAL
1.1    RELATED DOCUMENTS

A.    Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.

1.2    SUMMARY

A.    Section Includes:

1.    Concrete masonry units.
2.    Pre-faced concrete masonry units.
3.    Face brick.
4.    Building (common) brick.
5.    Mortar and grout.
6.    Masonry joint reinforcement.
7.    Ties and anchors.
8.    Embedded flashing.
9.    Miscellaneous masonry accessories.
10.    Cavity-wall insulation.

B.    Related Sections:

1.    Division 03 Section "Cast-in-Place Concrete" for installing dovetail slots for masonry anchors.
2.    Division 05 Section "Structural Steel Framing" for installing anchor sections of adjustable masonry anchors for connecting to structural steel frame.
3.    Division 05 Section "Metal Fabrications" for furnishing steel lintels and shelf angles for unit masonry.
4.    Division 07 Section "Sheet Metal Flashing and Trim" for exposed sheet metal flashing and for furnishing manufactured reglets installed in masonry joints.
5.    Division 08 Section "Louvers and Vents" for wall vents (brick vents).

1.3    DEFINITIONS

A.    CMU(s): Concrete masonry unit(s).

1.4    PERFORMANCE REQUIREMENTS

A.    Provide structural unit masonry that develops indicated net-area compressive strengths at 28 days.
 
1.    Determine net-area compressive strength of masonry from average net-area compressive strengths of masonry units and mortar types (unit-strength method) according to Tables 1 and 2 in ACI 530.1/ASCE 6/TMS 602.
2.    Determine net-area compressive strength of masonry by testing masonry prisms according to ASTM C 1314.

1.5    PRECONSTRUCTION TESTING

A.    Preconstruction Testing Service: Owner will engage a qualified independent testing agency to perform preconstruction testing indicated below. Retesting of materials that fail to comply with specified requirements shall be done at Contractor's expense.

1.    Clay Masonry Unit Test: For each type of unit required, according to ASTM C 67 for compressive strength.
2.    Concrete Masonry Unit Test: For each type of unit required, according to ASTM C 140 for compressive strength.
3.    Mortar Test (Property Specification):  For each mix required, according to ASTM C 109/C 109M for compressive strength, ASTM C 1506 for water retention, and ASTM C 91 for air content.
4.    Mortar Test (Property Specification): For each mix required, according to ASTM C 780 for compressive strength.
5.    Grout Test (Compressive Strength): For each mix required, according to ASTM C 1019.
6.    Prism Test: For each type of construction required, according to ASTM C 1314.

1.6    SUBMITTALS

A.    Product Data: For each type of product indicated.

B.    Shop Drawings: For the following:

1.    Masonry Units: Show sizes, profiles, coursing, and locations of special shapes.
2.    Fabricated Flashing: Detail corner units, end-dam units, and other special applications.

C.    Samples for Verification: For each type and color of the following:

1.    Exposed Decorative CMUs.
2.    Pre-faced CMUs.
3.    Face Hollow brick, in the form of straps of five or more bricks.
4.    Glazed brick.
5.    Pigmented and colored-aggregate mortar. Make Samples using same sand and mortar ingredients to be used on Project.
6.    Weep holes and vents.
7.    Accessories embedded in masonry.

D.    List of Materials Used in Constructing Mockups: List generic product names together with manufacturers, manufacturers' product names, model numbers, lot numbers, batch numbers, source of supply, and other information as required to identify materials used. Include mix proportions for mortar and grout and source of aggregates.
 
1.    Submittal is for information only. Neither receipt of list nor approval of mockup constitutes approval of deviations from the Contract Documents unless such deviations are specifically brought to the attention of Architect and approved in writing.

E.    Qualification Data: For testing agency.

F.    Material Certificates: For each type and size of the following:

1.    Masonry units.

a.    Include data on material properties and material test reports substantiating compliance with requirements.
b.    For brick, include size-variation data verifying that actual range of sizes falls within specified tolerances.
c.    For exposed brick, include test report for efflorescence according to ASTM C 67.
d.    For masonry units used in structural masonry, include data and calculations establishing average net-area compressive strength of units.

2.    Cementitious materials. Include brand, type, and name of manufacturer.
3.    Preblended, dry mortar mixes. Include description of type and proportions of ingredients.
4.    Grout mixes. Include description of type and proportions of ingredients.
5.    Joint reinforcement.
6.    Anchors, ties, and metal accessories.

G.    Mix Designs: For each type of mortar and grout. Include description of type and proportions of ingredients.

1.    Include test reports for mortar mixes required to comply with property specification. Test according to ASTM C 109/C 109M for compressive strength, ASTM C 1506 for water retention, and ASTM C 91 for air content.
2.    Include test reports, according to ASTM C 1019, for grout mixes required to comply with compressive strength requirement.

H.    Statement of Compressive Strength of Masonry: For each combination of masonry unit type and mortar type, provide statement of average net-area compressive strength of masonry units, mortar type, and resulting net-area compressive strength of masonry determined according to Tables 1 and 2 in ACI 530.1/ASCE 6/TMS 602.

I.    Cold-Weather and Hot-Weather Procedures: Detailed description of methods, materials, and equipment to be used to comply with requirements.

1.7    QUALITY ASSURANCE

A.    Testing Agency Qualifications: Qualified according to ASTM C 1093 for testing indicated.

B.    Source Limitations for Masonry Units: Obtain exposed masonry units of a uniform texture and color, or a uniform blend within the ranges accepted for these characteristics, from single source from single manufacturer for each product required.
 
C.    Source Limitations for Mortar Materials: Obtain mortar ingredients of a uniform quality, including color for exposed masonry, from single manufacturer for each cementitious component and from single source or producer for each aggregate.

D.    Masonry Standard: Comply with ACI 530.1/ASCE 6/TMS 602 unless modified by requirements in the Contract Documents.

E.    Sample Panels: Build sample panels to verify selections made under sample submittals and to demonstrate aesthetic effects. Comply with requirements in Division 01 Section "Quality Requirements" for mockups.

1.    Build sample panels for each type of exposed unit masonry construction typical exterior wall typical interior wall and typical exterior and interior walls in sizes approximately 48 inches (1200 mm) long by 48 inches (1200 mm) high by full thickness.
2.    Where masonry is to match existing, erect panels adjacent and parallel to existing surface.
3.    Clean exposed faces of panels with masonry cleaner indicated.
4.    Protect approved sample panels from the elements with weather-resistant membrane.
5.    Approval of sample panels is for color, texture, and blending of masonry units; relationship of mortar and sealant colors to masonry unit colors; tooling of joints; aesthetic qualities of workmanship; and other material and construction qualities specifically approved by Architect in writing.

a.    Approval of sample panels does not constitute approval of deviations from the Contract Documents contained in sample panels unless such deviations are specifically approved by Architect in writing.

1.8    DELIVERY, STORAGE, AND HANDLING

A.    Store masonry units on elevated platforms in a dry location. If units are not stored in an enclosed location, cover tops and sides of stacks with waterproof sheeting, securely tied. If units become wet, do not install until they are dry.

B.    Store cementitious materials on elevated platforms, under cover, and in a dry location. Do not use cementitious materials that have become damp.

C.    Store aggregates where grading and other required characteristics can be maintained and contamination avoided.

D.    Deliver preblended, dry mortar mix in moisture-resistant containers designed for use with dispensing silos. Store preblended, dry mortar mix in delivery containers on elevated platforms, under cover, and in a dry location or in covered weatherproof dispensing silos.

E.    Store masonry accessories, including metal items, to prevent corrosion and accumulation of dirt and oil.
 
1.9    PROJECT CONDITIONS

A.    Protection of Masonry: During construction, cover tops of walls, projections, and sills with waterproof sheeting at end of each day's work. Cover partially completed masonry when construction is not in progress.

1.    Extend cover a minimum of 24 inches (600 mm) down both sides of walls and hold cover securely in place.
2.    Where one wythe of multiwythe masonry walls is completed in advance of other wythes, secure cover a minimum of 24 inches (600 mm) down face next to unconstructed wythe and hold cover in place.

B.    Do not apply uniform floor or roof loads for at least 12 hours and concentrated loads for at least three days after building masonry walls or columns.

C.    Stain Prevention: Prevent grout, mortar, and soil from staining the face of masonry to be left exposed or painted. Immediately remove grout, mortar, and soil that come in contact with such masonry.

1.    Protect base of walls from rain-splashed mud and from mortar splatter by spreading coverings on ground and over wall surface.
2.    Protect sills, ledges, and projections from mortar droppings.
3.    Protect surfaces of window and door frames, as well as similar products with painted and integral finishes, from mortar droppings.
4.    Turn scaffold boards near the wall on edge at the end of each day to prevent rain from splashing mortar and dirt onto completed masonry.

D.    Cold-Weather Requirements: Do not use frozen materials or materials mixed or coated with ice or frost. Do not build on frozen substrates. Remove and replace unit masonry damaged by frost or by freezing conditions. Comply with cold-weather construction requirements contained in ACI 530.1/ASCE 6/TMS 602.

1.    Cold-Weather Cleaning: Use liquid cleaning methods only when air temperature is 40 deg F (4 deg C) and higher and will remain so until masonry has dried, but not less than seven days after completing cleaning.

E.    Hot-Weather Requirements: Comply with hot-weather construction requirements contained in ACI 530.1/ASCE 6/TMS 602.

PART 2 - PRODUCTS

2.1    MASONRY UNITS, GENERAL

A.    Defective Units: Referenced masonry unit standards may allow a certain percentage of units to contain chips, cracks, or other defects exceeding limits stated in the standard. Do not use units where such defects will be exposed in the completed Work.
 
B.    Fire-Resistance Ratings: Where indicated, provide units that comply with requirements for fire- resistance ratings indicated as determined by testing according to ASTM E 119, by equivalent masonry thickness, or by other means, as acceptable to authorities having jurisdiction.

2.2    CONCRETE MASONRY UNITS

A.    Regional Materials: Provide CMUs that have been manufactured within 500 miles (800 km) of Project site from aggregates and cement that have been extracted, harvested, or recovered, as well as manufactured, within 500 miles (800 km) of Project site.

B.    Shapes: Provide shapes indicated and as follows, with exposed surfaces matching exposed faces of adjacent units unless otherwise indicated.

1.    Provide special shapes for lintels, corners, jambs, sashes, movement joints, headers, bonding, and other special conditions.
2.    Provide square-edged or bullnose units for outside corners unless otherwise indicated.

C.    Integral Water Repellent: Provide units made with integral water repellent for exposed units and where indicated.

1.    Integral Water Repellent: Liquid polymeric, integral water-repellent admixture that does not reduce flexural bond strength. Units made with integral water repellent, when tested according to ASTM E 514 as a wall assembly made with mortar containing integral water-repellent manufacturer's mortar additive, with test period extended to 24 hours, shall show no visible water or leaks on the back of test specimen.

a.    Products: Subject to compliance with requirements, provide one of the following available products that may be incorporated into the Work include, but are not limited to, the following:

1)    ACM Chemistries; RainBloc.
2)    BASF Aktiengesellschaft; Rheopel Plus.
3)    Grace Construction Products, W. R. Grace & Co. - Conn.; Dry-Block.

D.    CMUs: ASTM C 90.

1.    Unit Compressive Strength: Provide units with minimum average net-area compressive strength of 2150 psi (14.8 MPa).
2.    Density Classification: Normal weight unless otherwise indicated.
3.    Size (Width): Manufactured to dimensions 3/8 inch less than nominal dimensions.

4.    Exposed Faces: Provide color and texture matching the range represented by Architect's sample.
5.    Faces to Receive Plaster: Where units are indicated to receive a direct application of plaster, provide textured-face units made with gap-graded aggregates.

2.3    CONCRETE AND MASONRY LINTELS

A.    General: Provide one of the following:
 
B.    Concrete Lintels: ASTM C 1623, matching CMUs in color, texture, and density classification; and with reinforcing bars indicated. Provide lintels with net-area compressive strength not less than CMUs.

C.    Concrete Lintels: Precast or formed-in-place concrete lintels complying with requirements in Division 03 Section "Cast-in-Place Concrete," and with reinforcing bars indicated.

D.    Masonry Lintels: Prefabricated or built-in-place masonry lintels made from bond beam CMUs with reinforcing bars placed as indicated and filled with coarse grout. Cure precast lintels before handling and installing. Temporarily support built-in-place lintels until cured.

2.4    BRICK

A.    General: Provide shapes indicated and as follows, with exposed surfaces matching finish and color of exposed faces of adjacent units:

1.    For ends of sills and caps and for similar applications that would otherwise expose unfinished brick surfaces, provide units without cores or frogs and with exposed surfaces finished.
2.    Provide special shapes for applications where stretcher units cannot accommodate special conditions, including those at corners, movement joints, bond beams, sashes, and lintels.
3.    Provide special shapes for applications requiring brick of size, form, color, and texture on exposed surfaces that cannot be produced by sawing.
4.    Provide special shapes for applications where shapes produced by sawing would result in sawed surfaces being exposed to view.

B.    Face Brick: Facing brick complying with ASTM C 216 or hollow brick complying with ASTM C 652, Class H40V (void areas between 25 and 40 percent of gross cross-sectional area).

1.    Grade: SW, MW or SW.
2.    Type: FBS.
3.    Unit Compressive Strength: Provide units with minimum average net-area compressive strength of 3350 psi (23.10 MPa).
4.    Initial Rate of Absorption: Less than 30 g/30 sq. in. (30 g/194 sq. cm) per minute when tested per ASTM C 67.
5.    Efflorescence: Provide brick that has been tested according to ASTM C 67 and is rated "not effloresced."
6.    Size (Actual Dimensions): 3-5/8 inches (92 mm) wide by 2-1/4 inches (57 mm) high by 7-5/8 inches (194 mm) long.
7.    Application: Use where brick is exposed unless otherwise indicated.
8.    Where shown to "match existing," provide face brick matching color range, texture, and size of existing adjacent brickwork.

9.    Color and Texture: As selected by Architect.

C.    Building (Common) Brick: ASTM C 62, Grade SW.

1.    Unit Compressive Strength: Provide units with minimum average net-area compressive strength of 3350 psi (23.10 MPa).
2.    Size: Match size of face brick.
 
3.    Application: Use where brick is indicated for concealed locations. Face brick complying with requirements for grade, compressive strength, and size indicated for building brick may be substituted for building brick.

2.5    MORTAR AND GROUT MATERIALS

A.    Portland Cement: ASTM C 150, Type I or II, except Type III may be used for cold-weather construction. Provide natural color or white cement as required to produce mortar color indicated.

B.    Hydrated Lime: ASTM C 207, Type S.

C.    Portland Cement-Lime Mix: Packaged blend of portland cement and hydrated lime containing no other ingredients.

D.    Masonry Cement: ASTM C 91.

1.    Products: Subject to compliance with requirements, available products that may be incorporated into the Work include, but are not limited to, the following:

a.    Capital Materials Corporation; Flamingo Color Masonry Cement.
b.    Cemex S.A.B. de C.V.; Brikset Type N, Citadel Type S, Dixie Type S, Kosmortar Type N, Richmortar, Victor Plastic Cement.
c.    Essroc, Italcementi Group; Brixment or Velvet.
d.    Holcim (US) Inc.; Mortamix Masonry Cement Rainbow Mortamix Custom Buff Masonry Cement White Mortamix Masonry Cement.
e.    Lafarge North America Inc.; Magnolia Masonry Cement Lafarge Masonry Cement Trinity White Masonry Cement.
f.    Lehigh Cement Company; Lehigh Masonry Cement Lehigh, White Masonry Cement.
g.    National Cement Company, Inc.; Coosa Masonry Cement.

E.    Mortar Cement: ASTM C 1329.

1.    Products: Subject to compliance with requirements, available products that may be incorporated into the Work include, but are not limited to, the following:

a.    Lafarge North America Inc.; Lafarge Mortar Cement or Magnolia Superbond Mortar Cement.

F.    Mortar Pigments: Natural and synthetic iron oxides and chromium oxides, compounded for use in mortar mixes and complying with ASTM C 979. Use only pigments with a record of satisfactory performance in masonry mortar.

1.    Products: Subject to compliance with requirements, available products that may be incorporated into the Work include, but are not limited to, the following:

a.    Davis Colors; True Tone Mortar Colors.
b.    Lanxess Corporation; Bayferrox Iron Oxide Pigments.
c.    Solomon Colors, Inc.; SGS Mortar Colors.
 
G.    Colored Cement Product: Packaged blend made from portland cement and hydrated lime and mortar pigments, all complying with specified requirements, and containing no other ingredients.

1.    Products: Subject to compliance with requirements, provide one of the following:

a.    Colored Portland Cement-Lime Mix:

1)    Capital Materials Corporation; Riverton Portland Cement Lime Custom Color.
2)    Holcim (US) Inc.; Rainbow Mortamix Custom Color Cement/Lime.
3)    Lafarge North America Inc.; Eaglebond Portland & Lime.
4)    Lehigh Cement Company; Lehigh Custom Color Portland/Lime Cement.

2.    Formulate blend as required to produce color indicated or, if not indicated, as selected from manufacturer's standard colors.
3.    Pigments shall not exceed 10 percent of portland cement by weight.
4.    Pigments shall not exceed 5 percent of masonry cement or mortar cement by weight.

H.    Aggregate for Mortar: ASTM C 144.

1.    For mortar that is exposed to view, use washed aggregate consisting of natural sand or crushed stone.
2.    For joints less than 1/4 inch (6 mm) thick, use aggregate graded with 100 percent passing the No. 16 (1.18-mm) sieve.
3.    White-Mortar Aggregates: Natural white sand or crushed white stone.
4.    Colored-Mortar Aggregates: Natural sand or crushed stone of color necessary to produce required mortar color.

I.    Aggregate for Grout: ASTM C 404.

J.    Cold-Weather Admixture: Nonchloride, noncorrosive, accelerating admixture complying with ASTM C 494/C 494M, Type C, and recommended by manufacturer for use in masonry mortar of composition indicated.

1.    Products: Subject to compliance with requirements, available products that may be incorporated into the Work include, but are not limited to, the following:

a.    Euclid Chemical Company (The); Accelguard 80.
b.    Grace Construction Products, W. R. Grace & Co. - Conn.; Morset.
c.    Sonneborn Products, BASF Aktiengesellschaft; Trimix-NCA.

K.    Water-Repellent Admixture: Liquid water-repellent mortar admixture intended for use with CMUs containing integral water repellent by same manufacturer.

1.    Products: Subject to compliance with requirements, available products that may be incorporated into the Work include, but are not limited to, the following:

a.    ACM Chemistries; RainBloc for Mortar.
b.    BASF Aktiengesellschaft; Rheopel Mortar Admixture.
 
c.    Grace Construction Products, W. R. Grace & Co. - Conn.; Dry-Block Mortar Admixture.

L.    Water: Potable.

2.6    REINFORCEMENT

A.    Uncoated Steel Reinforcing Bars: ASTM A 615/A 615M or ASTM A 996/A 996M, Grade 60.

B.    Masonry Joint Reinforcement, General: ASTM A 951/A 951M.

1.    Interior Walls: Hot-dip galvanized, carbon steel.
2.    Exterior Walls: Hot-dip galvanized, carbon steel.
3.    Wire Size for Side Rods: 0.187-inch (4.76-mm) diameter.
4.    Wire Size for Cross Rods: 0.187-inch (4.76-mm) diameter.
5.    Wire Size for Veneer Ties: 0.187-inch (4.76-mm) diameter.
6.    Spacing of Cross Rods, Tabs, and Cross Ties: Not more than 16 inches (407 mm) o.c.
7.    Provide in lengths of not less than 10 feet (3 m), with prefabricated corner and tee units.

C.    Masonry Joint Reinforcement for Single-Wythe Masonry:    Either ladder or truss type with single pair of side rods.

D.    Masonry Joint Reinforcement for Multiwythe Masonry:
1.    Adjustable (two-piece) type, either ladder or truss design, with one side rod at each face shell of backing wythe and with separate adjustable ties with pintle-and-eye connections having a maximum adjustment of 1-1/4 inches (32 mm). Size ties to extend at least halfway through facing wythe but with at least 5/8-inch (16-mm) cover on outside face. Ties have hooks or clips to engage a continuous horizontal wire in the facing wythe.

E.    Masonry Joint Reinforcement for Veneers Anchored with Seismic Masonry-Veneer Anchors: Single 0.187-inch- (4.76-mm-) diameter, hot-dip galvanized, carbon -steel continuous wire.

2.7    TIES AND ANCHORS

A.    Materials: Provide ties and anchors specified in this article that are made from materials that comply with the following unless otherwise indicated.
1.    Hot-Dip    Galvanized,    Carbon-Steel    Wire:    ASTM A 82/A 82M;    with ASTM A 153/A 153M, Class B-2 coating.
2.    Stainless-Steel Wire: ASTM A 580/A 580M, Type 304.
3.    Galvanized Steel Sheet:    ASTM A 653/A 653M, Commercial Steel, G60 (Z180) zinc coating.
4.    Steel Sheet, Galvanized after Fabrication: ASTM A 1008/A 1008M, Commercial Steel, with ASTM A 153/A 153M, Class B coating.
5.    Stainless-Steel Sheet: ASTM A 666, Type 304, Type 316.
6.    Steel Plates, Shapes, and Bars: ASTM A 36/A 36M.
 
B.    Wire Ties, General: Unless otherwise indicated, size wire ties to extend at least halfway through veneer but with at least 5/8-inch (16-mm) cover on outside face. Outer ends of wires are bent 90 degrees and extend 2 inches (50 mm) parallel to face of veneer.

C.    Individual Wire Ties: Rectangular units with closed ends and not less than 4 inches (100 mm) wide.

1.    Z-shaped ties with ends bent 90 degrees to provide hooks not less than 2 inches (50 mm) long may be used for masonry constructed from solid units.
2.    Where wythes do not align are of different materials, use adjustable ties with pintle-and- eye connections having a maximum adjustment of 1-1/4 inches (32 mm).
3.    Wire:    Fabricate from 1/4-inch- (6.35-mm-) diameter, hot-dip galvanized steel wire. Mill-galvanized wire ties may be used in interior walls unless otherwise indicated.

D.    Adjustable Anchors for Connecting to Structural Steel Framing: Provide anchors that allow vertical or horizontal adjustment but resist tension and compression forces perpendicular to plane of wall.

1.    Anchor Section for Welding to Steel Frame: Crimped 1/4-inch- (6.35-mm-) diameter, hot-dip galvanized steel stainless-steel wire. Mill-galvanized wire may be used at interior walls unless otherwise indicated.
2.    Tie Section: Triangular-shaped wire tie, sized to extend within 1 inch (25 mm) of masonry face, made from 0.25-inch- (6.35-mm-) diameter, hot-dip galvanized steel stainless-steel wire. Mill-galvanized wire may be used at interior walls unless otherwise indicated.

E.    Adjustable Anchors for Connecting to Concrete: Provide anchors that allow vertical or horizontal adjustment but resist tension and compression forces perpendicular to plane of wall.

1.    Connector Section: Dovetail tabs for inserting into dovetail slots in concrete and attached to tie section; formed from 0.060-inch- (1.52-mm-) thick, steel sheet, galvanized after fabrication 01.05-inch- (2.66-mm-) thick, steel sheet, galvanized after fabrication 0.062- inch- (1.59-mm-) thick, stainless-steel sheet 0.109-inch- (2.78-mm-) thick, stainless-steel sheet.

a.    0.108-inch- (2.74-mm-) thick, galvanized sheet may be used at interior walls unless otherwise indicated.

2.8    EMBEDDED FLASHING MATERIALS

A.    Metal Flashing: Provide metal flashing complying with SMACNA's "Architectural Sheet Metal Manual" Division 07 Section "Sheet Metal Flashing and Trim"" and as follows:

1.    Stainless Steel: ASTM A 240/A 240M, Type 304, 0.016 inch (0.40 mm) thick.
2.    Fabricate continuous flashings in sections 96 inches (2400 mm) long minimum, but not exceeding 12 feet (3.7 m). Provide splice plates at joints of formed, smooth metal flashing.
3.    Fabricate through-wall metal flashing embedded in masonry from stainless steel, with ribs at 3-inch (76-mm) intervals along length of flashing to provide an integral mortar bond.
 
a.    Products: Subject to compliance with requirements, provide one of the following:

1)    Cheney Flashing Company; or Cheney 3-Way Flashing (Sawtooth).
2)    Keystone Flashing Company, Inc.; Keystone 3-Way Interlocking Thruwall Flashing.
3)    Sandell Manufacturing Co., Inc.; Mechanically Keyed Flashing.

4.    Fabricate through-wall flashing with snaplock receiver on exterior face where indicated to receive counterflashing.
5.    Fabricate through-wall flashing with drip edge where indicated. Fabricate by extending flashing 1/2 inch (13 mm) out from wall, with outer edge bent down 30 degrees and hemmed.
6.    Fabricate through-wall flashing with sealant stop where indicated. Fabricate by bending metal back on itself 3/4 inch (19 mm) at exterior face of wall and down into joint 1/4 inch (6 mm) to form a stop for retaining sealant backer rod.
7.    Fabricate metal drip edges for ribbed metal flashing from plain metal flashing of same metal as ribbed flashing and extending at least 3 inches (76 mm) into wall with hemmed inner edge to receive ribbed flashing and form a hooked seam. Form hem on upper surface of metal so that completed seam will shed water.

B.    Solder and Sealants for Sheet Metal Flashings: As specified in Division 07 Section "Sheet Metal Flashing and Trim."

1.    Solder for Stainless Steel: ASTM B 32, Grade Sn60, with acid flux of type recommended by stainless-steel sheet manufacturer.
2.    Solder for Copper: ASTM B 32, Grade Sn50, 50 percent tin and 50 percent lead.
3.    Elastomeric Sealant: ASTM C 920, chemically curing silicone sealant; of type, grade, class, and use classifications required to seal joints in sheet metal flashing and trim and remain watertight.

C.    Adhesives, Primers, and Seam Tapes for Flashings: Flashing manufacturer's standard products or products recommended by flashing manufacturer for bonding flashing sheets to each other and to substrates.

2.9    MISCELLANEOUS MASONRY ACCESSORIES

A.    Compressible Filler: Premolded filler strips complying with ASTM D 1056, Grade 2A1; compressible up to 35 percent; of width and thickness indicated; formulated from neoprene.

B.    Preformed Control-Joint Gaskets: Made from styrene-butadiene-rubber compound, complying with ASTM D 2000, Designation M2AA-805 or PVC, complying with ASTM D 2287, Type PVC-65406 and designed to fit standard sash block and to maintain lateral stability in masonry wall; size and configuration as indicated.

C.    Bond-Breaker Strips: Asphalt-saturated, organic roofing felt complying with ASTM D 226, Type I (No. 15 asphalt felt).

D.    Weep/Vent Products: Use the following unless otherwise indicated:
 
1.    Mesh Weep/Vent: Free-draining mesh; made from polyethylene strands, full height and width of head joint and depth 1/8 inch (3 mm) less than depth of outer wythe; in color selected from manufacturer's standard.

a.    Products: Subject to compliance with requirements, available products that may be incorporated into the Work include, but are not limited to, the following:

1)    Mortar Net USA, Ltd.; Mortar Net Weep Vents.
2)    Archovations, Inc. CavClear Wee Vents.

E.    Cavity Drainage Material: Free-draining mesh, made from polymer strands that will not degrade within the wall cavity.

1.    Products: Subject to compliance with requirements, provide the following:

a.    Advanced Building Products Inc.; Mortar Break.
b.    Archovations, Inc.; CavClear Masonry Mat.
c.    Dayton Superior Corporation, Dur-O-Wal Division; Polytite MortarStop.
d.    Mortar Net USA, Ltd.; Mortar Net.

2.    Provide the following configurations:

a.    Strips, full-depth of cavity and 10 inches (250 mm) high, with dovetail shaped notches 7 inches (175 mm) deep that prevent clogging with mortar droppings.

2.10    CAVITY-WALL INSULATION

A.    Extruded-Polystyrene Board Insulation: ASTM C 578, Type IV, closed-cell product extruded with an integral skin.

B.    Adhesive: Type recommended by insulation board manufacturer for application indicated.

2.11    MORTAR AND GROUT MIXES

A.    General: Do not use admixtures, including pigments, air-entraining agents, accelerators, retarders, water-repellent agents, antifreeze compounds, or other admixtures, unless otherwise indicated.

1.    Do not use calcium chloride in mortar or grout.
2.    Use portland cement-lime masonry cement or mortar cement mortar unless otherwise indicated.
3.    For exterior masonry, use portland cement-lime masonry cement or mortar cement mortar.
4.    For reinforced masonry, use portland cement-lime masonry cement or mortar cement mortar.
5.    Add cold-weather admixture (if used) at same rate for all mortar that will be exposed to view, regardless of weather conditions, to ensure that mortar color is consistent.
 
B.    Preblended, Dry Mortar Mix: Furnish dry mortar ingredients in form of a preblended mix. Measure quantities by weight to ensure accurate proportions, and thoroughly blend ingredients before delivering to Project site.

C.    Mortar for Unit Masonry: Comply with ASTM C 270, Proportion Specification. Provide the following types of mortar for applications stated unless another type is indicated.

1.    For masonry below grade or in contact with earth, use Type M.
2.    For reinforced masonry, use Type S.
3.    For mortar parge coats, use Type N.
4.    For exterior, above-grade, load-bearing and non-load-bearing walls and parapet walls; for interior load-bearing walls; for interior non-load-bearing partitions; and for other applications where another type is not indicated, use Type N.
5.    For interior non-load-bearing partitions, Type O may be used instead of Type N.

D.    Pigmented Mortar: Use colored cement product or select and proportion pigments with other ingredients to produce color required. Do not add pigments to colored cement products.

1.    Pigments shall not exceed 10 percent of portland cement by weight.
2.    Mix to match Architect's sample.
3.    Application: Use pigmented mortar for exposed mortar joints with the following units:
a.    Pre-faced CMUs.
b.    Face brick.

E.    Colored-Aggregate Mortar: Produce required mortar color by using colored aggregates and natural color or white cement as necessary to produce required mortar color.

1.    Mix to match Architect's sample.
2.    Application: Use colored aggregate mortar for exposed mortar joints with the following units:
a.    Pre-faced CMUs.
b.    Face brick.

F.    Grout for Unit Masonry: Comply with ASTM C 476.

1.    Use grout of type indicated or, if not otherwise indicated, of type (fine or coarse) that will comply with Table 1.15.1 in ACI 530.1/ASCE 6/TMS 602 for dimensions of grout spaces and pour height.
2.    Proportion grout in accordance with ASTM C 476, or paragraph 4.2.2 for specified 28- day compressive strength indicated, but not less than 3000 psi.
3.    Provide grout with a slump of 8 to 11 inches (203 to 279 mm) as measured according to ASTM C 143/C 143M.

PART 3 - EXECUTION

3.1    EXAMINATION

A.    Examine conditions, with Installer present, for compliance with requirements for installation tolerances and other conditions affecting performance of the Work.
 
1.    For the record, prepare written report, endorsed by Installer, listing conditions detrimental to performance of work.
2.    Verify that foundations are within tolerances specified.
3.    Verify that reinforcing dowels are properly placed.

B.    Before installation, examine rough-in and built-in construction for piping systems to verify actual locations of piping connections.

C.    Proceed with installation only after unsatisfactory conditions have been corrected.

3.2    INSTALLATION, GENERAL

A.    Thickness: Build cavity and composite walls and other masonry construction to full thickness shown. Build single-wythe walls to actual widths of masonry units, using units of widths indicated.

B.    Build chases and recesses to accommodate items specified in this and other Sections.

C.    Leave openings for equipment to be installed before completing masonry. After installing equipment, complete masonry to match the construction immediately adjacent to opening.

D.    Use full-size units without cutting if possible. If cutting is required to provide a continuous pattern or to fit adjoining construction, cut units with motor-driven saws; provide clean, sharp, unchipped edges. Allow units to dry before laying unless wetting of units is specified. Install cut units with cut surfaces and, where possible, cut edges concealed.

E.    Select and arrange units for exposed unit masonry to produce a uniform blend of colors and textures.

1.    Mix units from several pallets or cubes as they are placed.

F.    Matching Existing Masonry: Match coursing, bonding, color, and texture of existing masonry.

G.    Wetting of Brick: Wet brick before laying if initial rate of absorption exceeds 30 g/30 sq. in. (30 g/194 sq. cm) per minute when tested per ASTM C 67. Allow units to absorb water so they are damp but not wet at time of laying.

3.3    TOLERANCES

A.    Dimensions and Locations of Elements:

1.    For dimensions in cross section or elevation do not vary by more than plus 1/8 inch or minus 1/8 inch.
2.    For location of elements in plan do not vary from that indicated by more than plus or minus 1/4 inch.
3.    For location of elements in elevation do not vary from that indicated by more than plus or minus 1/4 inch in a story height or 1/2 inch total.

B.    Lines and Levels:
 
1.    For bed joints and top surfaces of bearing walls do not vary from level by more than 1/4 inch in 10 feet (6 mm in 3 m), or 1/2 inch (12 mm) maximum.
2.    For conspicuous horizontal lines, such as lintels, sills, parapets, and reveals, do not vary from level by more than 1/8 inch in 10 feet (3 mm in 3 m), 1/4 inch in 20 feet (6 mm in 6 m), or 1/4 inch (12 mm) maximum.
3.    For vertical lines and surfaces do not vary from plumb by more than 1/8 inch in 10 feet, or 1/4 inch maximum.
4.    For conspicuous vertical lines, such as external corners, door jambs, reveals, and expansion and control joints, do not vary from plumb by more than 1/8 inch in 10 feet, or 1/4 inch maximum.
5.    For lines and surfaces do not vary from straight by more than 1/8 inch in 10 feet, or 1/4 inch maximum.
6.    For vertical alignment of exposed head joints, do not vary from plumb by more than 1/4 inch in 10 feet, or 1/2 inch (12 mm) maximum.
7.    For faces of adjacent exposed masonry units, do not vary from flush alignment by more than 1/16 inch (1.5 mm) except due to warpage of masonry units within tolerances specified for warpage of units.

C.    Joints:

1.    For bed joints, do not vary from thickness indicated by more than plus or minus 1/8 inch (3 mm), with a maximum thickness limited to 1/2 inch (12 mm).
2.    For exposed bed joints, do not vary from bed-joint thickness of adjacent courses by more than 1/8 inch (3 mm).
3.    For head and collar joints, do not vary from thickness indicated by more than plus 3/8 inch (9 mm) or minus 1/4 inch (6 mm).
4.    For exposed head joints, do not vary from thickness indicated by more than plus or minus 1/8 inch (3 mm). Do not vary from adjacent bed-joint and head-joint thicknesses by more than 1/8 inch (3 mm).
5.    For exposed bed joints and head joints of stacked bond, do not vary from a straight line by more than 1/16 inch (1.5 mm) from one masonry unit to the next.

3.4    LAYING MASONRY WALLS

A.    Lay out walls in advance for accurate spacing of surface bond patterns with uniform joint thicknesses and for accurate location of openings, movement-type joints, returns, and offsets. Avoid using less-than-half-size units, particularly at corners, jambs, and, where possible, at other locations.

B.    Bond Pattern for Exposed Masonry: Unless otherwise indicated, lay exposed masonry in running bond; do not use units with less than nominal 4-inch (100-mm) horizontal face dimensions at corners or jambs.

C.    Lay concealed masonry with all units in a wythe in running bond or bonded by lapping not less than 2 inches (50 mm). Bond and interlock each course of each wythe at corners. Do not use units with less than nominal 4-inch (100-mm) horizontal face dimensions at corners or jambs.

D.    Stopping and Resuming Work: Stop work by racking back units in each course from those in course below; do not tooth. When resuming work, clean masonry surfaces that are to receive
 
mortar, remove loose masonry units and mortar, and wet brick if required before laying fresh masonry.

E.    Built-in Work: As construction progresses, build in items specified in this and other Sections. Fill in solidly with masonry around built-in items.

F.    Fill space between steel frames and masonry solidly with mortar unless otherwise indicated.

G.    Where built-in items are to be embedded in cores of hollow masonry units, place a layer of metal lath, wire mesh, or plastic mesh in the joint below and rod mortar or grout into core.

H.    Fill cores in hollow CMUs with grout 24 inches (600 mm) under bearing plates, beams, lintels, posts, and similar items unless otherwise indicated.

I.    Build non-load-bearing interior partitions full height of story to underside of solid floor or roof structure above unless otherwise indicated.

1.    Install compressible filler in joint between top of partition and underside of structure above.
2.    Fasten partition top anchors to structure above and build into top of partition. Grout cells of CMUs solidly around plastic tubes of anchors and push tubes down into grout to provide 1/2-inch (13-mm) clearance between end of anchor rod and end of tube. Space anchors 48 inches (1200 mm) <Insert spacing> o.c. unless otherwise indicated.
3.    Wedge non-load-bearing partitions against structure above with small pieces of tile, slate, or metal. Fill joint with mortar after dead-load deflection of structure above approaches final position.
4.    At fire-rated partitions, treat joint between top of partition and underside of structure above to comply with Division 07 Section "Fire-Resistive Joint Systems."

3.5    MORTAR BEDDING AND JOINTING

A.    Lay hollow CMUs as follows:

1.    With face shells fully bedded in mortar and with head joints of depth equal to bed joints.
2.    With webs fully bedded in mortar in all courses of piers, columns, and pilasters.
3.    With webs fully bedded in mortar in grouted masonry, including starting course on footings.
4.    With entire units, including areas under cells, fully bedded in mortar at starting course on footings where cells are not grouted.

B.    Lay solid masonry units with completely filled bed and head joints; butter ends with sufficient mortar to fill head joints and shove into place. Do not deeply furrow bed joints or slush head joints.

3.6    MASONRY JOINT REINFORCEMENT

A.    General: Install entire length of longitudinal side rods in mortar with a minimum cover of 5/8 inch (16 mm) on exterior side of walls, 1/2 inch (13 mm) elsewhere. Lap reinforcement a minimum of 6 inches (150 mm).
 
1.    Space reinforcement not more than 16 inches (406 mm) o.c.
2.    Space reinforcement not more than 8 inches (203 mm) o.c. in foundation walls and parapet walls.

B.    Interrupt joint reinforcement at control and expansion joints unless otherwise indicated.

C.    Provide continuity at wall intersections by using prefabricated T-shaped units.

D.    Provide continuity at corners by using prefabricated L-shaped units.

E.    Cut and bend reinforcing units as directed by manufacturer for continuity at corners, returns, offsets, column fireproofing, pipe enclosures, and other special conditions.

3.7    ANCHORING MASONRY TO STRUCTURAL STEEL AND CONCRETE

A.    Anchor masonry to structural steel and concrete where masonry abuts or faces structural steel or concrete to comply with the following:

1.    Provide an open space not less than 1/2 inch (13 mm) wide between masonry and structural steel or concrete unless otherwise indicated. Keep open space free of mortar and other rigid materials.
2.    Anchor masonry with anchors embedded in masonry joints and attached to structure.
3.    Space anchors as indicated, but not more than 24 inches (610 mm) o.c. vertically and 36 inches (915 mm) o.c. horizontally.

3.8    ANCHORING MASONRY VENEERS

A.    Anchor masonry veneers to wall framing with seismic masonry-veneer anchors to comply with the following requirements:

1.    Fasten screw-attached anchors through sheathing to wall framing and to concrete and masonry backup with metal fasteners of type indicated. Use two fasteners unless anchor design only uses one fastener.
2.    Insert slip-in anchors in metal studs as sheathing is installed. Provide one anchor at each stud in each horizontal joint between sheathing boards.
3.    Embed connector sections and continuous wire in masonry joints. Provide not less than 2 inches (50 mm) of air space between back of masonry veneer and face of sheathing.
4.    Locate anchor sections to allow maximum vertical differential movement of ties up and down.
5.    Space anchors as indicated, but not more than 16 inches o.c. vertically and 24 inches (610 mm) o.c. horizontally, with not less than 1 anchor for each 2 sq. ft. (0.2 sq. m) of wall area. Install additional anchors within 12 inches (305 mm) of openings and at intervals, not exceeding 36 inches (203 mm), around perimeter.
 
3.9    CONTROL AND EXPANSION JOINTS

A.    General: Install control and expansion joint materials in unit masonry as masonry progresses. Do not allow materials to span control and expansion joints without provision to allow for in- plane wall or partition movement.

B.    Form control joints in concrete masonry as follows:
1.    Install temporary foam-plastic filler in head joints and remove filler when unit masonry is complete for application of sealant.

C.    Form expansion joints in brick as follows:
1.    Form open joint full depth of brick wythe and of width indicated, but not less than 1/2 inch (13 mm) for installation of sealant and backer rod specified in Division 07 Section "Joint Sealants."

D.    Provide horizontal, pressure-relieving joints by either leaving an air space or inserting a compressible filler of width required for installing sealant and backer rod specified in Division 07 Section "Joint Sealants," but not less than 3/8 inch (10 mm).

1.    Locate horizontal, pressure-relieving joints beneath shelf angles supporting masonry.

3.10    LINTELS

A.    Install steel lintels where indicated.

B.    Provide concrete or masonry lintels where shown and where openings of more than 12 inches (305 mm) for brick-size units and 24 inches (610 mm) for block-size units are shown without structural steel or other supporting lintels.

C.    Provide minimum bearing of 8 inches (200 mm) at each jamb unless otherwise indicated.

3.11    FLASHING, WEEP HOLES, CAVITY DRAINAGE, AND VENTS

A.    General: Install embedded flashing and weep holes in masonry at shelf angles, lintels, ledges, other obstructions to downward flow of water in wall, and where indicated, and upward flow of air in cavities, and where indicated.

B.    Install flashing as follows unless otherwise indicated:

1.    Prepare masonry surfaces so they are smooth and free from projections that could puncture flashing. Where flashing is within mortar joint, place through-wall flashing on sloping bed of mortar and cover with mortar. Before covering with mortar, seal penetrations in flashing with adhesive, sealant, or tape as recommended by flashing manufacturer.
2.    At multiwythe masonry walls, including cavity walls, extend flashing through outer wythe, turned up a minimum of 8 inches (200 mm), and 1-1/2 inches (38 mm) into the inner wythe. Form 1/4-inch (6-mm) hook in edge of flashing embedded in inner wythe.
 
3.    At masonry-veneer walls, extend flashing through veneer, across air space behind veneer, and up face of sheathing at least 8 inches (200 mm); with upper edge tucked under building paper or building wrap, lapping at least 4 inches (100 mm).
4.    At lintels and shelf angles, extend flashing a minimum of 6 inches (150 mm) into masonry at each end. At heads and sills, extend flashing 6 inches (150 mm) at ends and turn up not less than 2 inches (50 mm) to form end dams.
5.    Interlock end joints of ribbed sheet metal flashing by overlapping ribs not less than 1-1/2 inches (38 mm) or as recommended by flashing manufacturer, and seal lap with elastomeric sealant complying with requirements in Division 07 Section "Joint Sealants" for application indicated.
6.    Install metal drip edges with ribbed sheet metal flashing by interlocking hemmed edges to form hooked seam. Seal seam with elastomeric sealant complying with requirements in Division 07 Section "Joint Sealants" for application indicated.
7.    Cut flexible flashing off flush with face of wall after masonry wall construction is completed.

C.    Install single-wythe CMU flashing system in bed joints of CMU walls where indicated to comply with manufacturer's written instructions. Install CMU cell pans with upturned edges located below face shells and webs of CMUs above and with weep spouts aligned with face of wall. Install CMU web covers so that they cover upturned edges of CMU cell pans at CMU webs and extend from face shell to face shell.

D.    Install reglets and nailers for flashing and other related construction where they are shown to be built into masonry.

E.    Install weep holes in head joints in exterior wythes of first course of masonry immediately above embedded flashing and as follows:

1.    Use specified weep/vent products to form weep holes.
2.    Use wicking material to form weep holes above flashing under brick sills. Turn wicking down at lip of sill to be as inconspicuous as possible.
3.    Space weep holes 24 inches (600 mm) o.c. unless otherwise indicated.
4.    Space weep holes formed from plastic tubing or wicking material 16 inches (400 mm) o.c.
5.    Cover cavity side of weep holes with plastic insect screening at cavities insulated with loose-fill insulation.
6.    Trim wicking material flush with outside face of wall after mortar has set.

F.    Place pea gravel in cavities as soon as practical to a height equal to height of first course above top of flashing, but not less than 2 inches (50 mm), to maintain drainage.

1.    Fill cavities full height by placing pea gravel in cavities as masonry is laid so that at any point masonry does not extend more than 24 inches (600 mm) above top of pea gravel.

G.    Place cavity drainage material in cavities to comply with configuration requirements for cavity drainage material in "Miscellaneous Masonry Accessories" Article.

H.    Install vents in head joints in exterior wythes at spacing indicated. Use specified weep/vent products or open head joints to form vents.
 
1.    Close cavities off vertically and horizontally with blocking in manner indicated. Install through-wall flashing and weep holes above horizontal blocking.

3.12    REPAIRING, POINTING, AND CLEANING

A.    Remove and replace masonry units that are loose, chipped, broken, stained, or otherwise damaged or that do not match adjoining units. Install new units to match adjoining units; install in fresh mortar, pointed to eliminate evidence of replacement.

B.    Pointing: During the tooling of joints, enlarge voids and holes, except weep holes, and completely fill with mortar. Point up joints, including corners, openings, and adjacent construction, to provide a neat, uniform appearance. Prepare joints for sealant application, where indicated.

C.    In-Progress Cleaning: Clean unit masonry as work progresses by dry brushing to remove mortar fins and smears before tooling joints.

D.    Final Cleaning: After mortar is thoroughly set and cured, clean exposed masonry as follows:

1.    Remove large mortar particles by hand with wooden paddles and nonmetallic scrape hoes or chisels.
2.    Test cleaning methods on sample wall panel; leave one-half of panel uncleaned for comparison purposes. Obtain Architect's approval of sample cleaning before proceeding with cleaning of masonry.
3.    Protect adjacent stone and nonmasonry surfaces from contact with cleaner by covering them with liquid strippable masking agent or polyethylene film and waterproof masking tape.
4.    Wet wall surfaces with water before applying cleaners; remove cleaners promptly by rinsing surfaces thoroughly with clear water.
5.    Clean brick by bucket-and-brush hand-cleaning method described in BIA Technical Notes 20.
6.    Clean masonry with a proprietary acidic cleaner applied according to manufacturer's written instructions.
7.    Clean concrete masonry by cleaning method indicated in NCMA TEK 8-2A applicable to type of stain on exposed surfaces.

END OF SECTION 042000
 

Back to Top